Planning and Practical Exploration of Endoscopy Center Construction Scheme
I. Introduction to the Functions of the Endoscopy Center
An endoscopy center typically refers to a medical technology platform that integrates the functions of endoscopic examination, diagnosis, and treatment using flexible endoscopes. Flexible endoscopes are mainly divided into digestive endoscopy, respiratory endoscopy, urological endoscopy, otolaryngological endoscopy, and gynecological endoscopy, corresponding to the examination or treatment of diseases of the digestive, respiratory, urinary, otolaryngological, and gynecological systems. They are widely used clinically and have gradually become a mainstay of minimally invasive techniques.
During the initial design phase of this project, the hospital decided to construct an endoscopy center in the outpatient unit using a “digestive endoscopy + respiratory endoscopy” model. Flexible endoscopes for other clinical specialties, including otolaryngological and gynecological endoscopy, will operate independently within their respective outpatient unit areas. Laparoscopes (rigid endoscopes) will be managed centrally by the operating department. This article analyzes the initial planning process of the endoscopy center in the renovation and expansion project of Wenzhou Central Hospital’s Shuangyu branch and elaborates on the author’s strategic suggestions for implementing the endoscopy center construction plan.
1. Construction Scale and Content
After multiple rounds of consultation and discussion, the construction scale of this project is tentatively set at a total building area of no less than 2,500 square meters for the endoscopy center. The construction content needs to include a digestive endoscopy unit, a gastrointestinal motility unit, and a respiratory endoscopy unit. Following the recommendations of the <<China Hospital Construction Guidelines>>, the overall layout should include an office and living area (12%-15% of the area), a patient waiting area (6%-8% of the area), an anesthesia recovery area (6%-8% of the area), a treatment area (50%-55% of the area), a cleaning, disinfection, and storage area (10%-12% of the area), and a waste disposal area (6%-8% of the area). Specific requirements for each area are as follows:
The office and living area should be uniformly set up, including changing rooms for medical staff, offices, demonstration rooms, meeting rooms, rest rooms, duty rooms, storage rooms, and restrooms.
The patient waiting area will be shared by the digestive endoscopy unit and the gastrointestinal motility unit, with a nurses’ station. The respiratory endoscopy unit will have a separate patient waiting area with a nurses’ station.
The anesthesia recovery area should have separate recovery areas and nurse stations for gastrointestinal endoscopy and respiratory endoscopy. The ratio of anesthesia recovery beds to an anesthesia/sedation endoscopy operating room should be no less than 1:1, and preferably controlled within the range of 1:1.5-1:2.5. Specifically, the gastrointestinal endoscopy room should have an anesthesia preparation room and an anesthesia recovery room with a minimum of 10-15 beds, while the respiratory endoscopy room should have a separate anesthesia preparation room and an anesthesia/sedation recovery room with a minimum of 2-3 beds.
Treatment Areas –
1. Digestive Endoscopy Unit: Approximately 500 square meters, including at least 10 painless gastrointestinal endoscopy rooms (including endoscopic ultrasound (EUS) and endoscopic submucosal dissection (ESD)), and one endoscopic retrograde cholangiopancreatography (ERCP) room, with a storage room.
2. Gastrointestinal Motility Unit: Approximately 200 square meters, including 4 digestive endoscopy rooms (1 for upper gastrointestinal tract, 1 for lower gastrointestinal tract, 1 for fetal microbiota transplantation (FMT), and 1 gastrointestinal treatment room), plus one electrogastrography room, one expiratory chamber, two consultation rooms, and one capsule endoscopy room.
3. Respiratory Endoscopy Unit: Approximately 140 square meters, including at least 2 bronchoscopy rooms (with negative pressure ventilation), with a storage room.
The digestive endoscope and respiratory endoscope cleaning and storage areas should each have separate cleaning and disinfection rooms and endoscope storage rooms.
The waste disposal area should ideally have a unified waste washing room and waste temporary storage room.
Other supporting functional rooms – space should be allocated for supporting functional rooms such as carbon dioxide cylinder rooms, UPS rooms, water treatment rooms, and equipment rooms.
2. Flow Design Requirements
The overall layout should be designed according to a “five-zone, three-channel” system. The five zones are the waiting area, treatment area, anesthesia recovery area, endoscope cleaning and disinfection storage area, and office/living area. The three channels are the flow lines for medical staff, patients, and waste (including endoscope processing). The waiting area, treatment area, anesthesia recovery area, and cleaning and disinfection area for digestive and respiratory endoscopes should be relatively independent to avoid cross-infection. The flow line for medical staff should meet the basic site conditions. The medical staff elevator should be located on the northwest side, and the office/living area should be located nearby, with consideration given to lighting and ventilation.
Patient flow needs to be convenient for functional units closely related to the endoscopy center, such as outpatient, emergency, inpatient, radiology, pathology, operating room, and ICU. The internal flow within the center is as follows: waiting and reception → pre-examination preparation → examination and treatment → post-operative recovery → departure.
The waste flow line must be set up separately and not intersect with other flow lines. For endoscope washing and disinfection, gastroscopes and colonoscopes should be washed separately, following the transfer sequence of washing and disinfection area → drying area → storage area, with separate functional rooms for each.
3. Other Special Design Requirements
In designing the endoscopy center, in addition to complying with relevant design standards and normative documents, the design unit should also meet the following requirements:
1. The water treatment room, UPS room, and washing and disinfection room need to have increased structural load-bearing capacity. Once the location is determined in the design phase, it will not be adjusted in the construction phase. Therefore, it is recommended to place them in the corners of auxiliary functional areas to reduce the difficulty of future secondary modifications.
2. The water supply and drainage and equipment installation in the washing and disinfection room have special requirements. It is recommended to introduce multiple professional manufacturers to jointly arrange a common solution in the design phase to avoid secondary modifications required during the construction phase to accommodate equipment procurement.
3. The endoscopy center needs to be equipped with an independently operating air conditioning system. A variable frequency multi-split air conditioning system or an independent centralized cold and heat source air conditioning system is recommended. An air conditioning group control system should also be configured and linked with intelligent engineering to facilitate future integration with the intelligent logistics management platform. Each area has temperature and humidity control requirements.