Area requirements and design considerations for hospital disinfection supply centers

The Central Sterile Supply Department (CSSD) is a department within a hospital responsible for cleaning, disinfecting, sterilizing, and supplying sterile items to all reusable medical instruments, equipment, and supplies for various departments.

Location

1. Ideally located near operating rooms, delivery rooms, and clinical departments, or with a dedicated passageway for direct transport of items between the location and the operating room.

2. Suitable for locations with good natural lighting but avoiding excessive sunlight and good ventilation; not suitable for underground or semi-underground locations.

area

1. Basic Requirements. The facility must comply with relevant construction regulations and be compatible with the hospital’s scale, nature, tasks, and development.

2. Simplified Total Area Standard. The center area can be determined based on a bed-to-bed ratio of (0.6-0.9):1. For example, the floor area of ​​a 600-bed hospital’s disinfection supply center should be: 600 x (0.6-0.9 m²/bed) = 360-540 m².

3. Reference Values ​​for Zoning Areas. (1) Decontamination area: 22-30% of the total supply room area; (2) Inspection, packaging, and sterilization area: 40-50% of the total supply room area; (3) Sterile goods storage area: 8%-10%; (4) Auxiliary areas (staff office and living areas): 10%-15% of the supply room area.

4. Minimum Area, i.e., the area sufficient to accommodate essential facilities, equipment, and personnel activity space.

5. Factors affecting the area that can be considered during the design process include the quantity and type of reusable medical devices to be processed, the type and area of ​​mechanical cleaning equipment, the inventory and turnover of sterile items, and the calculation of area and operating costs.

Floor plan

The facility includes a work area and an auxiliary area.

1. The work area includes a decontamination area, an inspection, packaging, and sterilization area (including a dressing room), a sterile supplies storage area, and storage and disposal rooms for tools required for each area. The decontamination area includes a contaminated instrument receiving area, a personnel access buffer room (larger than 5 square meters), a goods transfer window, goods racks, and handwashing facilities.

2. The auxiliary area includes a living area and an office area, including changing rooms, restrooms, a duty room, a meeting (training) room, offices, and a storage room.

Key Design Considerations

1. Water Supply

1) The ambient water pressure should be 196–294 kPa (2–3 kgf/cm²), the water quality should meet drinking water standards, and the water temperature should be below 0℃.

2) The hot water circulation temperature should be above 50℃; a shut-off valve and pressure gauge should be installed after the main hot and cold water supply pipes enter the CSSD.

3) Purified water treatment equipment is used for the rinsing process of reusable medical devices; the conductivity of purified water should be ≤15 μS/cm (25℃).

2. Power Supply

1) High-power equipment should have a separate power supply box, such as pulsed vacuum sterilizers and fully automatic cleaning and disinfection equipment.

2) Sufficient electrical capacity should be reserved according to the development plan of the CSSD.

3. Steam

1) Ensure the purity of the steam to guarantee the sterilization effect; the steam transport pipes should be pressure-resistant, high-temperature resistant, and rust-proof.

2) The steam pipes should be sealed with heat-insulating cotton to reduce the phenomenon of wet packaging of sterilized items and avoid reducing steam efficiency. 3) Drain valve installation: A drain valve is installed at the lowest point of the pipeline before the steam enters the steam sterilizer to ensure that condensate is discharged in a timely manner when the steam sterilizer is not in use.

4. Drainage

1) Regarding floor drains, straight-through floor drains with filters and water seals, plus water traps, are suitable; separate floor drains should be installed in the decontamination area; floor drains are not required in the sterile goods storage area, inspection and packaging area, and sterilization area.

2) Regarding drain pipes, pulsed vacuum sterilizers should have separate drains to prevent poor drainage and wet packaging; cleaning and disinfection equipment should have independent drain pipes with a diameter not less than DN75; piping for hot water discharge equipment should be made of high-temperature resistant materials.

3) Regarding wastewater treatment, wastewater from the main equipment in the decontamination area should be discharged into a centralized wastewater treatment system.

5. Cleanroom-related indicator requirements refer to the requirements of the current industry standard WS310. Key points include:

1) Cleanliness level: Cleanroom (inspection, packaging and sterilization area and sterile goods storage area) Level 8.

2) Air exchange rate: 10h-1

3) Pressure difference: The decontamination area should maintain a relative negative pressure; the inspection, packaging and sterilization area and sterile goods storage area should maintain a relative positive pressure.

4) Temperature and humidity: The temperature in the decontamination area should be between 18 and 20°C; the temperature in the inspection and packaging area and the sterile goods storage area should be between 20 and 23°C. The relative humidity should generally be between 45% and 65%, unless otherwise specified.